Search

Search

Locking by the handle

The following manual operators can be locked by the handle:

Up to three padlocks with a shackle diameter of between 5 and 8 mm can be used to lock the rotary operators. Padlocks are not included in the scope of supply.

Front mounted rotary operator

59429220491.png

Lockable switching positions:

Door mounted rotary operator and side wall mounted rotary operator

56874079627.png

Lockable switching positions:

NOTE

No impairment of protection functions

Locking the rotary operators in the ON (I) position does not impair the protective functionality of the molded case circuit breakers. In the event of a fault, the molded case circuit breaker trips in the normal way.

When the rotary operator is unlocked, the switching position changes to TRIP.